GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

boiler will not turn off (only manually)glow-worm micron 80ff?

when the programmer has switched off , the boiler continues to run (until I switch it off manually) we have changed thermostat,pump,programmer and most other items, other than the boiler. We have had 2 heating enginners and 1 electrician, they all say it can't be the boiler . any Ideas .
Bill (in despair) Camberley , Surrey., November 2013
obviously you need to trace why the boiler is getting a feed when it shouldn't, the first thing that comes to mind is a zone valve, if there are 2-2port valves the orange wires should not be live when both valves are closed,try disconnecting them ( the orange wires ) and powering up to see what happens,as I find in lot of cases like this the supposed experts do not apply any logic to the fault finding process I mean why change the pump it has nothing to do with firing the boiler up.If the fault persists you need to trace why it is getting a fire up signal, from the boiler back to source,not hard job to somebody who knows what they are doing

toptrish, November 2013
link Click here to see other fixes for Glow-Worm.