narnia asked ... Matsui ct-111ss?    |    Jason asked ... How to fix handset problems ( intercom ) and access control?    |    andy asked ... Samsung VP-D60 camcorder?    |    Shopper asked ... Poor Renault Radio Reception?    |    reg bardle asked ... Lg 7kg dd?    |    Click here to ask your question

Pressure rise?

Hi can anybody have any ideas regarding the climb in pressure on a solaris 30c
It climbs to 2.9/30 on the c/h side then the blue light flashes I then turn it off, leave it for 30 mins then I have to turn it back at a lower c/h temp
to get it to work, any tips

regards sammy
Sammythespan, November 2013
Either filling loop letting by or faulty expansion vessel

Sutdog, November 2013
Built into the boiler is an oblong expansion vessel,there is an air valve that should be accessible,open pressure relief valve to drop the pressure in the central heating system,then check the air pressure in the expansion vessel
as you would a car tyre then if needed pump up to 1.0 bar If pressure starts to increase again when its running the expansion vessel could need replacing

toptrish, November 2013