Karen asked ... Royal 480nt cash register?    |    andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    Click here to ask your question

how can i fix my boiler /Ideal logic+35?

repressurised boiler but after a while pressure drops again there is no vissiable sighns of leaks
phil, December 2013
constant pressure loss
no visible signs of leaks

check colour of water in condensate trap

if its CLEAR then there must be a leak on the system

if its RUSTY BROWN then very bad news
MAIN HEAT EXCHANGER IS LEAKING INTERNALLY
no other option than to replace HEX
part number 175615
job for qualified gas engineer only

Q, January 2014
may be pressure relief valve is faulty did you notice any water going out side from over flow pipe from boiler ,change valve

ltd, December 2013