GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Radiators are not working on my Glowworm Compact Electronic?

The radiators are not working on my Glowworm Compact Electronic combi-boiler. I,m getting hot water but no radiators heating up. The light next to the radiator sign has gone off. The pressure hasn,t changed and only one of the copper pipes coming from underneath is warm - I assume the hot water pipe. It also sounds like it is running constantly - before the radiators stopped working it would fire up and I could hear it running only when it was set by the timer to come on, but now even when it isn't set at the timer, it sounds like its running.
Fiona, December 2006
Hiya this is a common problem with this boiler, the problem you have is the water flow switch is sticking,if that does not turn right off it will not allow the heating to start,...how to fix ?
When you drop the front panel (2 screws) , you will see 2 black rectangular boxes,one left, one right,(about 2 inches x 1 inch) the problem one is the left one , it is held on by a big circlip,prise it off and on the valve underneath you will see a spindle sticking out,if there is sign's of water then you must change the unit,as the washer will have split, but usually its just a case of dirt causing it to stick,put some vaseline or wd40 on the spindle and with a pair of pliers,pull it gently in and out,the re-attach the black box with the circlip,it is worth doing the other switch at the same time(on right near pump)hopefully that will solve the problem,..ps be sure to turn of the electricity to the boiler first.... good luck

Barry Richardson, December 2006