Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Jerry asked ... Alpine 7287?    |    Guy asked ... Gaggenau fridge alarm problem?    |    Click here to ask your question

heating?

The PRV is leaking constantly with no heating on? is it the plate heat exchanger or the the expansion vessal. The filling loop is not passing. Ferroli Domi Condense HE26 c The prv is faulty i know that because it is dripping even at 1 bar of presure. But the guage keeps going up to 3 bar with no heating on
George Phillipson, July 2014
Are you absolutely sure the filling loop is not responsible,disconnect it to make sure.If its ok then the likely thing will be the heat exchanger. Underneath the boiler there is a 15mm pipe for the cold feed,there is an isolator valve that can be closed,close it then drop pressure to 1 then see if it rises,if not its the heat exchanger

toptrish, July 2014