GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Glow-worm flexicom24cx combination boiler?

My newly installed boiler is showing "fault 22" and the problem is low pressure. This is a new boiler and I replaced the old one because of the same problem. My gas engineer and warned me as he said there is a leak somewhere. As I live in a flat over a garage and have had this problem for at least 5 years I have found no evidence of a leak! HELP
Mrs Linda Millett, December 2006
what kind of plumber is he. there is a valve under the boiler called a prv that can be letting water by. which should have a pipe coming from it to an outside wall . they only release above 3 bar but if there grit in the seal can cause them to leak all the time

hi-spec, December 2006
Good answer I have no idea where the overflow is neither does the plumber. I guess it might be routed through the waste pipe. Is that possible?

mrs millett, December 2006
is it not leaking out overflow through outside wall

hi-spec plumbing, December 2006