GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Baxi 105HE - Heating comes on with water?

Heating has been turned off for summer but it comes on when any hot water is used either in kitchen or bathroom. Plumber has tried new pcb board and diaphram
Frances White, July 2016
Diverted valve is passing allowing the water which should be circulating around the hot water circuit to leak into the heating side.

Ian, August 2016
Manual here:

http://www.plumbcenter.co.uk/wcsstore7.00.00.549/ExtendedSitesCatalogAssetStore/images/products/AssetPush/DTP_AssetPushHighRes/std.lang.all/ti/on/Baxi_Combi105HE_Installation.pdf

Read fault analysis on Page 16

Flog through one step at a time, thinking logically.

It LOOKS like - on the basis of what I understand at the moment - that there is a problem around the bit that says "Continuity across DHW flow microswitch terminals and PCB - A5 connector terminals 5 & 6"

Read and think.

XXX, July 2016
link Click here to see other fixes for Baxi 105HE.