GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Is my boiler a write off?

My 8 year old Baxi 105he appears to have a crossover between the hot water and heating system. When the heating is on the pressure goes through the roof and the pressure valve opens and stays open with a constant flow of water that can fill a bucket in an hour! When heating is off the pressure drops to zero over about 30 mins. Is this a cracked heat exchanger or can the two systems interact if any other part has failed?? Thanks
Steve c, April 2018
Thanks snorky you were spot on. Fixed in 10 minutes with a foot pump! So much for the “Engineer” that wanted to fit a new boiler for £1450!!

Steve c, April 2018
The expansion vessel is either flat and needs recharging or is perished and needs replacing. The pressure relief valve will need cleaning and maybe replacing. Get an engineer to visit..

Snorky, April 2018