why does it still not work?

Having recently fitted a new air pressure switch to a "Vokera Excell 80sp" it still does not work, i can get it to fire up if i disconect one of the tubes and suck on it but as soon as i replace the tube the boiler cuts out, could it be the p.c.b? as the fault seems to indicate that it is the air pressure switch? many thanks m.edwards.
mr m edwards, January 2007
take the fan out look down into the fan outlet theirs a tee that connects to the red tube its blocked.without taking the fan completely out u will not see it.

paul also a gas man, January 2007
either the fan is very dirty, the venturi the hoses connect to on the fan are blocked or very dirty or there is a problem with the flue.

Paul the gas man, January 2007