Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

upstairs radiators only heating up at bottom of radiator?

hi my radiators are working downstairs but the upstairs ones only heat at bottom part,ive tried bleeding them but they dont seem to fill up,you can hear the water filling up but it doesnt actually fil,anyone know why?
are the radiators water pressure fed or is there a pump in my combi boiler that supplies it
andy wilson, March 2007
It is air that is causing your problem, but be advised that when you bleed them you will have to make sure that you top up the boiler pressure aswell. I always top up combis/condensers to about 1 to 1 1/2 bar.

Andy, March 2007
what boiler is it

hi-spec plumbing, March 2007
Is the pressure low on the dial?, if so top up with filling loop (silver braided pipe) below 2 bar, now try bleeding rads again. Water should weep out with no bubbles, recheck pressure, this should be about 1.5bar with all air out of system and cold. When running hot around 2 bar......
Hope this helps.

clfgas, March 2007