andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

DHW fault on Ferolli Modena 102?

I have a ferolli modena 102 combi and have recently noticed the hot water temperature is not what it used to be. The temp adjuster on front panel makes very little or no difference. I have asked a plumber who said to check thermister and flow switch. I have changed both of these for known good ones yet I still have the fault, any ideas please? One more thing,the water temperature while not hot, is more than luke warm and is constant.
DJO, March 2007
heat exchanger may be scaled up

hi-spec plumbing, March 2007
link Click here to see other fixes for Ferroli Modena 102.