Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

Worcester 350 combi boiler?

How do I get the water pressure back up over 1 bar? Pressure has dropped and can't work out how to alter it.
Neil, May 2007
There should be a flexible metal clad hose somewhere just below the boiler going from the cold main pipe to the central heating pipe.
On the cold end will be a tap. Some are like a washing machine tap with a plastic lever, others have a screwdriver slot.
You need to turn the tap on until the pressure gets to about 1 to 1.5 bar. Make sure you turn it back off.
If the boiler has run very low you might have to bleed some of your radiators. Then you'll need to top the pressure up again.
Best to do this with the boiler switched off and cold .

T.h.s, May 2007