3 hours ago Karen asked ... Royal 480nt cash register?    |    andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    Click here to ask your question

the dreaded ariston question?

i still have a ariston euro combi a/23.
i was told the air pressure switch may be at fault for the lack of constant hot water, when the sealed panel is removed and the hot water run it stays hot/the boiler continues to run .
as soon as the seald panel is put back the burner goes out and it cools down before re-igniting. is the fault so easy i can't see?
roy, February 2005
remove fan and clean blades. also check pipes on to air pressure switch + check the flue outside for debris or damage, problem sounds like air pressure differential not correct

Ryan, February 2005