Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Click here to ask your question

how can i fix my Ariston Microgenus gas boiler?

when i switch the boiler on; the fan comes on but does not light up. e34 shows up.
paul, July 2007
The air pressure switch is not closing

could be
low pressure differential between flue inlet and outlet caused by

leak in the tubing or tube/fan connection
leaking fan seal or not seated properly
Dirty fan
blockage in the flue inlet or outlet

OR defective pressure switch (diaphragm or switch)

andy, July 2009
e34 represents an air pressure switch problem...I suggest checking the aps tube from aps to fan for a blockage....probably blocked with water

IAN DITCHBURN, July 2007