GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Fixinf mt Ferroli F30 - and stop it overflowing?

i have a Ferroli F30, its two years old and have not had a problem till today. I know how to top up the water pressure and have done so but its not holding the pressure and its overflowing outside - solutions or ideas please!
Dave, July 2007
it may well be the pressure release valve that has not reseated you can try opening it manually by turning it till it snaps shut if this does not stop it running you will have to replace it....or does the pressure keep rising when you have heating on till it reaches 3bar? if so then your expansion vessel has gone you can either fit a new one but this will mean taking boiler off wall to do, then refitting, or you can fit a remote expansion kit as close to the boiler as poss. on the heating pipework, if it is the expansion vessle i really recommend tha you get an engineer in to at least get advice. good luck

sean, July 2007
link Click here to see other fixes for Ferroli F30.