katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Click here to ask your question

Re-connection of radiator, help?

The brackets for my radiator failed which meant I had to remove the radiator, and in the process drain the radiator.

I am in the process of trying to re-connect the radiator back onto the wall.

Do I need to fill up the pressurised combi with more water or just put the radiator back on wall and switch on the comi??? Theres a red metal container behind the comi...

if i've to put water in, how do I know who much water to put in ?

Cheers

Craig
Craig Miles, July 2007
After refitting rad and opening rad valves,rad will need to be vented through vent screw at the end up top or the rear.system pressure will drop.open filling loop,located under boiler or in hot press,recognisable by flexible hose,refill system to 1 or 1.5 bar.