1 hour ago Andrew asked ... Jcb cordless 20v combi drill?    |    marc asked ... La machine 1 type 813?    |    Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Click here to ask your question

Suanier Duval boiler (F24E) cannot decrease pressure?

The S.D. boiler in my new flat won't operate because the pressure is way too high. I have tried bleeding a radiator and using the relief valve which will lower the pressure while the mains supply is shut off, but as soon as I turn the mains back on up goes the pressure again. I've tried turning the mains on just a little bit but that doesn't work.
Barry Latchford, August 2007
is the filling loop letting by,make sure both valves are shut under boiler, your boiler has a built in filling loop.
if that fails the dhw heat exchanger is letting by to the primary circult.

hi-spec plumbing, August 2007