GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

switchmaster mid valves?

how do i re wire the old switch master valve for a honeywell model. the old switchmaster valve has 6 wires and the honeywell only has five wires. will this valve work on my system or do i need a plumber to do this.
swampy, March 2005
switchmaster 3port valve to honeywell

SwitchMaster(Blue{Neutral})-New Valve(Blue)
SwitchMaster(Green/Yellow{Earth})-New Valve(Green/Yellow)
SwitchMaster(Red{S/Live})-Link to Orange
SwitchMaster(Orange{HW On})-New Valve(Orange)
SwitchMaster(White{HW Off})-New Valve(Grey)
SwitchMaster(Yellow{CH On})-New Valve(White)

PETER, March 2009
SwitchMaster(Blue{Neutral})-New Valve(Blue)
SwitchMaster(Green/Yellow{Earth})-New Valve(Green/Yellow)
SwitchMaster(Red{S/Live})-Link to Orange
SwitchMaster(Orange{HW On})-New Valve(Orange)
SwitchMaster(White{HW Off})-New Valve(Grey)
SwitchMaster(Yellow{CH On})-New Valve(White)

The Red wire is now dropped on the more modern mid-position valves, you will find that this wire switched the boiler and pump on using the old switchmaster midi valve.

Instead now you need to connect the orange wire to the pump live and boiler live when wiring the new valve into the ten way.

Jonny Jones, December 2008
red and orange on switchmaster to orange on h/w yellow on s/m to white on h/w white on s/m to grey on h/w then neutrals and earths

d....m, April 2005
It is easy enough if you tell me what wires are on each valve on new valves there are always only five wires, blue, green ,white, grey and orange

Steve, March 2005
link Click here to see other fixes for Switchmaster.