Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

switchmaster mid valves?

how do i re wire the old switch master valve for a honeywell model. the old switchmaster valve has 6 wires and the honeywell only has five wires. will this valve work on my system or do i need a plumber to do this.
swampy, March 2005
switchmaster 3port valve to honeywell

SwitchMaster(Blue{Neutral})-New Valve(Blue)
SwitchMaster(Green/Yellow{Earth})-New Valve(Green/Yellow)
SwitchMaster(Red{S/Live})-Link to Orange
SwitchMaster(Orange{HW On})-New Valve(Orange)
SwitchMaster(White{HW Off})-New Valve(Grey)
SwitchMaster(Yellow{CH On})-New Valve(White)

PETER, March 2009
SwitchMaster(Blue{Neutral})-New Valve(Blue)
SwitchMaster(Green/Yellow{Earth})-New Valve(Green/Yellow)
SwitchMaster(Red{S/Live})-Link to Orange
SwitchMaster(Orange{HW On})-New Valve(Orange)
SwitchMaster(White{HW Off})-New Valve(Grey)
SwitchMaster(Yellow{CH On})-New Valve(White)

The Red wire is now dropped on the more modern mid-position valves, you will find that this wire switched the boiler and pump on using the old switchmaster midi valve.

Instead now you need to connect the orange wire to the pump live and boiler live when wiring the new valve into the ten way.

Jonny Jones, December 2008
red and orange on switchmaster to orange on h/w yellow on s/m to white on h/w white on s/m to grey on h/w then neutrals and earths

d....m, April 2005
It is easy enough if you tell me what wires are on each valve on new valves there are always only five wires, blue, green ,white, grey and orange

Steve, March 2005