GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

BAXI 105 HE PRESSURE DROP?

HI I HAVE FITTED A BAXI 105 HE INSTANT COMBI BOILER BUT THE SYSTEM PRESSURE KEEPS DROPPING I HAVE BLEAD ALL RADIATORS BUT WHEN I CHARGE SYSTEM TO 1.5 BAR AFTER A COUPLE OF DAYSIT DROPS BELOW 1 BAR I CANT FIND ANY LEAKS I HAVE GOT THE SELF BLEEDING SCREW ON THE BOILER CONSTANTLY OPEN THE RADIAORS GET RED HOT AND DOMESTIC WATER GETS RED HOT

ANY BODY GOT ANY IDEAS

CHEERS SHAUN
SHAUN POULSTON, October 2007
You definately have a leak somewhere. Firstly, check that the Pressure relief valve (PRV) is not letting water by.

If you cannot see it then it could be under the ground floor. You can put a leak sealer (fernox do one) into the central heating system, this can be squirted into a radiator and when you turn the system on, it should find any microscopic leaks and seal them - this may work.

Failing that, one easy way to find out whether the leak is on the boiler or on the pipework is to turn the valves off for the flow and return to the boiler (make sure you switch the boiler off first), leave it for a day - if the pressure doesn't drop then you know the leak is on the pipework, if it drops then it's leakig from the boiler.

Good luck.

Craig, October 2007
link Click here to see other fixes for Baxi.