Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

how to fix fault on ariston he 28 .fault code A77?

how to fix fault on ariston he 28. fault code A77 condensate trap full of water
chrisfoster, November 2007
Sorry also if the boiler is not hanging straight (leaning slightly to the left) it causes condensate water to build up against the sensor causing it to short across the points. Levelling out boiler and removing restrictor should do the trick.

Lee, January 2008
My plumber has changed a number of items to no avail, however after taking everything apart he found that the boiler had been installed with a restrictor in the flue. According to Ariston this is a big no no on this type of installation as it causes excessive condensation to be produced which it is not designed to cope with. Restrictor has been removed and to date no more problems. Fingers crossed.

Lee, January 2008
Have not got the answer but have the same problem. Will let you know what to do if I can get it fixed. Can you do the same?
Thanks Lee

Lee, December 2007