Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Nick asked ... Oven spark Continuing after lit?    |    Click here to ask your question

I have a Vaillant turbomax VUW 242E?

I have a valliant turbomax vuw 242e... The problem is that the pressure is reaching 3 bar.... I have tried bleeding water out of the radiators , this causs it to drop but it the climbes again.. could it be water in the expansion vessell?
Lont, December 2007
Check your expansion vessel, try turning your cold water inlet valve off - see if it rises then, if yes then there is a leak on the domestic heat exchanger, normally if this is the case then the pressure would continue to rise all the time.

Big A, December 2007
Thanks... I have checked the loop and it isnt drawing any water into the boiler.

lont, December 2007
First I would disconnect the filling loop in case it is continuously allowing fresh water into the boiler.

John, December 2007