Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Nick asked ... Oven spark Continuing after lit?    |    Click here to ask your question

Baxi Combi 105 HE condenser boiler pump question?

Can any one point me in the right direction with regards to the pump operation after the CH shuts down after boiler reaches the room stat temp.
My boliers pump constantly runs after the boiler has shut down when it reaches the stats temp. I understand that the pump will shut down after a few mins, but my pump still runs until the boiler fires up again.
The pump works 100% on the HW side.
So is this problem the CH temp sensor or on the PCB. The boiler worked fine until the CH differential valve valve stuck. The diaphragm was changed , and the problem of low system pressure/ fault on pump was cured.
Any advice would be appreciated.
Vince, December 2007
yes sounds like thermister is shot,try swaping thermister from hot water side and fire up this will show if its working or not

skipy, January 2010
link Click here to see other fixes for Baxi.