By current standards and Good practice An immersion heater should have its own circuit, As said on normal 240volt the 3Kw Element takes 13A but if you have a local volt drop and end up with less volts The Current drawn will be higher, In practice a 13A DP Fused spur will only have the same effect as the plug It will get hot and bothered and could possible cause a fire, but a fuse spur is in the wall and If its a stud wall the effects could be far worse, Hense a seperate circuit with a 16A Breaker With 2.5 Twin & Earth To a 20A Double Pole Switch And a 2.5mm Heat Resistant Flex Between the Element Connections and The said Unit, the current method Could be causing/have caused damaged to the cables connected to the socket, Basically Leave it alone and get the whole thing checked by a Approved Electrician, (usually one in your local pub)