GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

RCD problems?

i changed a consumer unit and put the 2 lighting on the switch side of the split load and the ring on the RCD side but the down stairs lighting is triping the RCD
Didcup, February 2008
Hi,
it is possible that you have mixed the Neutral wires up. In other words you have connected the lighting circuit neutral onto the RCD section of the neutral bar. This will cause the trip to operate when any light on this circuit is turned on. Check that the lighting neutrals are connected only to the 'Unprotected' side of the neutral bar. The remainder of the power circuits should be connetced to the RCD protected section of the neutral bar. Make sure that the two sections of the neutral bar are NOT linked together.

chunkeymonkey52, March 2008
should of done it how it should be done.

l m electrics., February 2008