GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

What rate wire should i power a 240v garage though?

2 questions please

Ive built a double garage and it needs power
Is this conduit suitable for running under ground ??

http://www.screwfix.com/prods/97987/Electrical/Conduit/Rigid-Conduit/Conduit-Pack-90m-Black

Also what rate wire should i run to the garage to cope with 6 florescent strip lights and 6 double sockets alog with 5 outside lights and electric gates??

Thanks
james, March 2008
I would suggest a 10mm Armoured.(SWA)

However you are breaking the law doing this yourself you need to be a Part P qualified electrician.
You CAN do it yourself but then it has to be signed off and a Partp certificate issued by the council building inspector.This applies particulalry to supplies going outside

With great respect if you need to ask a question like this you shouldnt be doing it.

Regards

Steve

Steve, March 2008
(1) The conduit looks OK. It should be buried at least 750 mm deep and for extra safety you could put timber - say a 6x1 rough board - over the conduit for extra protection. Warning tape laid in the trench, 300 mm above the conduit would also be a good idea.
(2) You need to specify the load. You also need to specify how far away the garage is from the point of supply (the house). The longer the cable, the greater it's resistance and you are supposed to ensure that the voltage drop is no more than 4% of the nominal supply voltage. A very long cable might have to be increased to the next higher cross-sectional area to prevent excessive voltage drop.
Assume 5 outside lights at 500 W each = 2500 W at 240 V is just under 13A. Your sockets will be protected (against overcurrent) by a 20 A mcb. Don't know what your electric gate is rated at so you would need a cable for 33A anyway. Assuming a PVC insulated, copper conductor in a conduit buried undergorund, a 4mm2 cable is the minimum required.
To allow for future expansion, a 6mm2 cable would be a good idea. Items such as electric welders which some people might have, would increase these figures considerably.
You would probably have a sub- consumer unit in the garage with a 35A switch fuse unit. The sockets in the garage need to be protected by their own 30mA RCD.

J, March 2008
Pleaser take this kindly but assuming that you are in the UK, what you are proposing may be illegal under Building Regs as you will be running power outside and you are obviously not a 'competent person' under the Act. Have you had the local inspector check the work so far? I'd suggest a call to your local authority as you may encounter problems when you try to sell the property.

t, March 2008