GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

can you help me with my worcester highflow 400 electronic combi ?

Just been round side of house and noticed pipe coming out the wall from back of combi is leaking water, please can anyone tell me what this means ?. ps the boiler has been working fine up to now but i am concerned at leak.
veronica, March 2008
Hi Veronica,

That pipe os the overflow pipe, when the boilers water pressure exceeds 3bar (safety limit) it lifts and reduces pressure by allowing water to live the system via this pipe.

When your system is totally cold, check your boiler system water pressure, should be between 1 - 1.5 bar, if it is much higher than this, make sure your filling loop is turned off, and drain water from your system via a radiator bleed valve until the pressure reads 1 - 1.5 bar.

If it reads 1 - 1.5bar, but when the system is running it increases to 3bar or above, then your system expansion vessel may need replacing, call a gas service tech. out to do this for you.

T, March 2008
link Click here to see other fixes for Worcester.