Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

F24 error code on valliant thermo boiler?

what does the F24 error code mean
DEBBIE EVANS, April 2008
F24 = dry fire protection (temp gradient of flow NTC too steep)

Possible causes: air in boiler or system, pump blocked or defective, pump output too low, blocked or partially blocked heat exchanger, sludged up system.

Basically, what it is saying, when the boiler fires, the water temp on the flow pipe increases so quickly the boiler sees something is wrong with either the volume of water (air in system) or the flow of water not being enough (pump / heat exchanger / sludged system)