Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

how can i fix my glow worm 30 cxi?

Hi,

I have a glow worm 30cxi boiler and have a problem that hopefully someone can help with.

The problem was that the heating was working fine but the hot water would work for a few mins then go cold if you turned the tap off waited 5 mins then you would get a little more hot water.

I checked with the manual and it said to check the 3 way diverter switch to take it out and see if the spindle moves in and out. I did check this and there was no movement at all. I returned the valve to the system and now the water seems to be better stays hotter for longer but not working how it should butttttt now I have no heating. could all this be due to the diverter switch its just I dont want to pay the £109 + vat for the switch if it isnt that causing the problem.

I have noticed that when you try to turn the heating on the boiler operates as normal but no heat available in radiators but when you turn the heat off the red light appears on boiler and flashes f14 for a few seconds,

Any help at all would be great

The boiler is approx 2 years old and complete rubbish the amount of repairs on it is beyond relief as listed below.

2 main pcb boards

heat exchanger seals

thermastat

and many other little switches,
roisin mcnab, May 2008
hi i hav a problem with the heating part of the boiler the hot water works fine but the heating will not stay on for more that a few seconds
i fitted a new rad and it worked great but the next day nothing i can not get the red light to go off on the digistat scr and i can not get the termastat to work with the rf tryed what it says in the manual but nothing
the bar is set at 1.1

d a lowe, May 2010
f14 is blocked domestic heatexchanger, bloked due to dirty heating system water, needs removing and cleaning. removing the diverter valve motor head? testing the spindle? leaving the lead attached to the motor then switching between heat'/water you can feel and see it move when in your hand.
did you put the motor back in correctly when you removed it??????

boilerman, May 2008