andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

Baxi Solo 3?

The "boiler on" led comes on only to indicate power to the boiler. The fan does not come on or anything else. The Boiler position has just been moved. Water pressure is at 1 bar. (Is this critical),
Chris, May 2008
see if you have power to the fan if you do you may have a seized fan this is a fail safe the boiler will do nothing if the dosen't run

der, May 2008
no, water pressure on a solo is not critical, have you got any external controls? (ie room stats,timers, zone valves?) if so ensure all are calling for heat or wire them out at the boiler to test the boiler only.

also, make sure the polarity is correct (ie. live is live, and neutral is neutral) when you switch on make sure the pump is running......