Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Click here to ask your question

Netaheat failure to ignite?

Netaheat 10/16 Mk 2 has developed a fault.
When the boiler is activated either manually or by the timer the fan starts and after a few seconds there is a click. Presumably some sort of pressure switch responding to the pressure inside the boiler. But thats it .... No repeat clicking noise as the pilot tries to light and therefore no boiler ignition.
Any suggestions would be greatly appreciated.
Many thanks
Trevor, May 2008
From the Fault Finding Chart from Potterton it would indicate that the pressure switch needs replacing. You should check if there is 240v across T4 & T6 on the electronic control. If not this confirms the diagonsis.

Ian, June 2008