Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

reponse 80 ideal boiler help?

Hi

I really hope someone can help me. just moved into a property and boiler has been working fine, both heating and hot water. However last night the 'low system pressure' led came on and now it's not producing any hot water.

It's an Ideal response 80 combi boiler

Can someone tell me how to top up the pressure?

Everything is boxed in at the min so I can't see much apart from dials and switches in the control which appear to be of no use in this case!

Any help greatly appreciated

Elaine
Elaine, June 2008
Thank you so much. All sorted now. I wouldn't have had a clue otherwise.

Thanks again

Elaine, June 2008
locate the filling loop (usually a flexible braided hose with small handle, that comes fromt he mains water to to system water, check for it under the boiler) slowly open and raise pressure to 1-15bar when system is cold, if you over pressure, bleed excess off at a radiator

T, June 2008