andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

the pressure on my 20/80 flowmatic keeps rising?

hi there the pressure on my boiler keeps going up and blows off leaving me with no hot water until i turn the pressure relief valve and bring the pressure back down to 1 and a half bars. whats wrong with it and how do i fix it? thanks
andrew, June 2008
also, just to add, you should never use the 3bar safety valve to lower pressure, at some stage it will not reseat and will dripp forever until replaced!

either use the boiler drain valve or bleed from a radiator

T, June 2008
The filling loop valve (that allows you to pressurise the system after maintenance) isn't fully closing on this one, I feel. Check that its fully turned off.

John, June 2008