Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

Icon 23T High Pressure problem, no hot water?

Hi, I have an icon 23T boiler, which is constantly on >4Bar pressure and off the scale, not the hot water dont come on, and the fault light isnt on either, any ideas on how to fix this?
Russ, July 2008
Yes, sorry I never made it clear in my question, but you answered anyway! I have bled the excess from a Rad, and it keeps increasing slowly over a day or 2.

Thanks Very Much for answering.

Russ, July 2008
reduce pressure by bleeding excess from a radiator, if the pressure increases again, your filling loop may be passing, remove it and try again, if successful, replace filling loop, if it still happens, you will need to get the dhw heat exchanger replaced as there is a leak between the primary and secondary waterways

T, July 2008