andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

Ravenheat RSF 820/20T?

Hi folks the water pressure has dropped dramatically and is well below the advised 1 bar. How do I increase this?
Pete, July 2008
Hi Pete,
you should have a filling loop as this is a closed system, so you should be looking for a flexi hose which attaches to one of your C/H pipes (this should be a one way valve ie it will let water in but not out). at the other end of the flexi should be a valve which you open to let water in, fetch it up to the right pressure and bleed off your rads and then top up as your pressure will drop in the system.
hope this helps

Darron, August 2008