Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

help with worcester junior combi boiler please?

my boiler is only four years old but has the last few weeks had an periodical problem with no hot water.when i check the pressure is low/only half bar?can anyone tell me how to top it up?underneath there is a loop with a screwhead both sides.And if i do this will it solve this problem?i believe the pressure should be between one and two??please help its driving me mad!!!!
Hannie, August 2008
The loop you see has a tap on it from mains pressure. Open the tap until the pressure reaches around 2 bar then close it again. If you go above around 3 bar it will vent off to the outside, so about 2 1/2 bar maximum before you turn it off. You may have a very slight leak somewhere that is losing the pressure. There is usually a rust mark or similar where the leak is.

Trev, August 2008