GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

LINEA 24 HELP NEEDED?

My linea 24 boiler pressure should run in the blue at 1 to 1.5 But the pressure is building up to 3 I bleed of at a radiator to get it back down but after about 12 hours it goes back up .The heating is not on.Had one answer from Steve,He says he thinks it is leaking via cold water loop top up if so how would you go about checking. Or any other suggestions thanks
Michael.Eaton, August 2008
Disconnect the cold water loop and see if water is coming out of the cold feed pipe,you may need to fit a new stop tap.

Gasman, August 2008