Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

i have a valiant ecotech it is showing f75 ?

it is not firing up i have turned it of and on and still the same can anyone give me a tip to try
claire, September 2008
Find a competent engineer who is able diagnose the fault to be the pressure sensor and explain why. Other wise it will be the build up of sludge and debris from the radiators in boiler that is affecting the sensor - best of luck

Dosta, September 2008
From Vaillant manual.

F.75 No pressure rise was detected on turning on the pump Water pressure sensor or/and pump defective
Too little water in appliance; check adjustable by-pass;

May be a stuck or faulty pump also check pressure guage is at least 1 bar

Ian, September 2008