3 hours ago Karen asked ... Royal 480nt cash register?    |    andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    Click here to ask your question

too much pressure in boiler goes to three bars ?

vokera mynute 20e. pressure goes to three bars and continues to rise when boiler is left on. I have bled the rads and this has made no difference. i have replaced a noisy acuator and problem is still there.
paul, October 2008
If boiler only increasing in pressure when heating is on then your expansion vessel is burst or needing recharged. If increase in pressure when boiler is off then filling loop passing.

Robert adam, October 2008
filling loop letting by ?

dave the rave, October 2008
Make sure the filling loop is off, and not letting by.

matt, October 2008
link Click here to see other fixes for Vokera mynute 20e.