GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

worcester heatslave 15/19 combination oil boiler?

hi we have had no heating now for 3wks could anyone tell me whats wrong with my boiler i have hot water but no heating .when heating is switched on it gets hot at the radiator valve end on the rad closest to the boiler then it goes no further.we have had many new parts on this boiler it was practically rebuilt last year by worcester.we have had a plumber out he put a new pump on but still no joy he says the motor is working fine the only thing that he can think is the radiators all need flushing out.can any one help or had simalar problem as this plumber charges £40.00 an hour!!!!!!!!!
zoe, October 2008
we 've just had the same problem our worcester engineer fixed our problem in 20 minutes by replacing diverter valve it pays to have the contract.

jimmy lindsay, September 2012
We had a similar problem and it was down to a faulty valve, which is common in this model. The valve sticks and you either have water and no heating or heating and no water. Our problem was solved after a new valve was fitted. Hope this helps.

Sue Jenkins, February 2011
hi I changed my diverter valve on my worcester 15/19 but had a bit of a flood i sorted it but now it wont fire up can you HELP please . Nick

Nick, January 2010
i am a heating engineer, and own a heatslave 15/19

this fault it usually the diverter valve sticking (its a common problem as mine goes every 2 years) the motorised head will be fine, you can pick the valve up for about £40 from merchants/web and its easy to change with a few screwdrivers and adjustable spanners (remember to drain the water out of the system first though else you will be getting wet!!)
to prevent it sticking again it is advisable to run your heating for a couple of mins each week (even in the summer) just to keep the valve free

Rusky, January 2009
Hi,
I have had simililar problems with my own same boiler several times. Usually it has been electrical parts but not always. To be honest you should phone worster bosch it will cost you £250 but they will replace up to 6 major parts. They have come out to me about 4 times but in each case they have fitted more than that amount in parts every time. If your paying a plumber who is second guessing at £40 ph it would be the cheapest option in the long run and it will be fixed

steve. G, November 2008
A plumber will charge that amount which sounds like a standard amount. When the boiler is put in the manufacturer states that systems need flushing out to remove sludge otherwise it will knacker the heat exchanger. Power pump flush outs with a machine cost anywhere between £345-£500 depending on how many rads are in the property! If worcester have replaced parts your lucky and the other problem you've got is that the boiler is a worcester, even their own engineers will tell you they're cr*p boilers!!!

Andy, October 2008
does not make sense unless the plumbing is wrong what i would suggest is you close off nearest rad and see if next rad gets warm if not it could be ch thermisitor on boiler let me know how you get on hallrichard69@yahoo.com

ricardo, October 2008