Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

WHAT IS CAUSING PRESSURE PROB ON RAVENHEAT CSI85 BOILER?

NOW THAT WEATHER IS COLDER I HAVE TURNED UP HEATING AND PRESSURE IS RISING OCCASIONALY TO THE POINT WHERE IT WEEPS OUT THE PRESSURE RELIEF VALVE CLOSE TO 3BAR.AFTER THIS IT OPERATES NORMALLY.COULD IT BE A STICKY PUMP? OR COULD SLUDGE IN THE SYSTEM BE CAUSING INTERMITTENT TROUBLE? OTHERWISE IT WORKS PERFECTLY WELL.
STEVIE, November 2008
sounds like your pressure vessel has gone, will need to drop pressure in system then charge to 1 bar using foot pump ect, if not charge bladder gone and whole unit will need replacing

jlkheating, November 2008