Katie Bond asked ... Fixing auto threader on Baby Lock Enlighten Overlocker?    |    Chris. asked ... Miele W800 novotronic washing machine?    |    Larry asked ... How to stop my steam iron from leaking. Model dw2463 Rowenta?    |    HT asked ... Radio code Philips 22RC200/35?    |    Roberta asked ... DW5080?    |    Click here to ask your question

the water pressure on my ch is in the red area ?

how do i decrease the water pressure in my ch system
nathan, November 2008
if the pressure guage is reading high you need to drain some water out of the central heating system until the reading is about 1bar,do this with the system turned off, then check to see if the fill point is passing or maybe the expansion vessel is either low charged or needs replacing