Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

the system cuts out at 3 bar bleeding isn't lowering?

newly fitted combi bolier shows 3 bar and cuts out as designed to do. bleeding the system doesn't help. what now?
mike m, December 2008
A bit short on info here but it sounds like your pressure vessel doesn't have enough air in it. This PV has to be pressurised by pumping it up so that as the water in the system heats and expands the air is squashed and the pressure stays within limits. Your system sounds like the PV has insufficient air in it. You can normally pump these up with a hand pump but you need to do it when there is no pressure on the water side. Once you've pressurised the PV correctly then you can use the filling loop to fill the system to its normal cold pressure. Hope that helps!

Richard, December 2008
Call the installer back

kutch, December 2008