Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

worchester boiler 24i problem ?

worchester boiler 24i problem ,how high should the pressure bar go up when radiators are on.mine is on 1bar but when switched on goes up to 4bar,is this normall.
kevin, December 2008
normally 1 or 1.5b check to see if water is running out your safety valve when heating is on normally a 15mm pipe outside somewhere if water is running out it may be a faulty pressure vessel or it may be choked

john, December 2008