2 hours ago Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    Click here to ask your question

Baxi Combi 105 HE Pressure Gauge Fault? Continued ?

Hi b, thanks for your response 'when you say the filling loop letting by' i have checked both taps and both are turned off (cold water inlet/heating return), could there be a fault with the cold water inlet? and if so, is this something that i'm going to have to get an engineer to come out and fix? Thanks Bekki :o)
Bekki, December 2008
if you disconnect the filling loop and the pressure still rises, then you have a problem with the plate heat exchanger. assuming you are topping it up to 1bar and the pressure rises when the boiler is not operating

Paul the gasman, December 2008