Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    Click here to ask your question

fault diagnosis?

worcester 28cd1 boiler drops pressure daily to 0.5 and requires daily topping up, have checked and found no leaks is pressure vessel at fault
n j north, January 2009
the boiler is displaying ea and not working what can i do to fix it?

tony, December 2010
worcester bosch boiler cutting out saying ea on display panel pilot light cutting out

andy, January 2009
Unless your system pressure is also getting very high (3bar) when hot then the PV is probably ok. The pv is designed to accomodate the increase in pressure so it should go up from say 2bar cold to 2.5bar hot. If it starts at 1.5bar cold and goes up to 3bar hot then the pv is not working and needs re charging or replacing. Don't forget there is a presure relief valve in the system and the seal on this can fail causing a gradual leak and so loss of pressure. Good luck

Richard, January 2009