As per table 4D4A it can handle 29A, assuming you're burying it directly in the ground, so you would be restricted to 25A.
Given that you're planning to run a lighting circuit from the same cable, volt drop constraints would restrict you to 8.3A.
Remember this would be notifiable to building control and must be carried out by a part P registered company.
Adam, February 2009