Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Katie Bond asked ... Fixing auto threader on Baby Lock Enlighten Overlocker?    |    Chris. asked ... Miele W800 novotronic washing machine?    |    Click here to ask your question

my buderus combi needs topping up every 15 mins. I've bled the rads?

my boiler constantly needs refilling
kev, February 2009
if your loosing pressure its very likley your loosing water.
check your radiators for leaks and all your pipework.
check your pressure relief pipe which normally discharges outside. if that is leaking you will need a pressure relief valve.
you will need to make sure your boiler is not over pressurising (3 bar on gauge)
if you have experienced a loss of pressure a few times and then increased pressure (excessive) your expansion vessel is likley to be faulty .

tech boiler svs, February 2009