Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Stuart G asked ... C3 Front Wiper control problem?    |    Clare S asked ... Repair Electriq dehumidifier?    |    Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Click here to ask your question

Valiant Pressure problem ?

I have valiant ecomax 828 and pressure on c/h rises to 3 bar when heating is on but drops to 0 when off. I think this is due to lack of pressure in expansion vessel? If so how easy is it to repressurise and to what pressure ?
Ian C, March 2009
drain water from boiler and recharge expansion vessel at shrader valve on expansion vessel... precharge to 0.75 bar if it won't take charge probably got a hole in the diaphragm
may also need to change pressure relief valve

dazza, March 2009