katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Click here to ask your question

worcester digistat for 28cdi?

I have just installed a worcester digistat to my boiler, i followed all instructions to the letter.
The unit learned correctly and the signal is clear and lights up as it should do but the boilers radiator light (and heating system) will not work.....even on overide the radiator light just flashes once per second.... the red button does not clear this, can anyone help please?
Richard Smith, April 2009
look for a link between the Ls and LR connections on the boiler, this is probably where your old hard wired room stat was wired in.

If there is no link, the new digistat won't work. Stick a link in and it should work.

Bunslinger, April 2009