Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Stuart G asked ... C3 Front Wiper control problem?    |    Clare S asked ... Repair Electriq dehumidifier?    |    Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Click here to ask your question

Potterton Prima 40f?

Boiler ignites and burners come on with 10mbar burner pressure. However looking through the view glass I get flame lift off. I have changed the fan cleared the pilot assembly blown through the air pressure tubes and checked out the integrity of the flue. I still get flame lift off followed by the burners going out.This cycle then continues. Help
Jack, May 2009
Rotted Flue terminal causing recirculation of stale flue gas, flame lifts off due to lack of oxygen. cure?
Potterton make a flue renovation kit for this boiler which consists of a pipe sleeve and new terminal and takes about 1 hour to fit

www.elanar.co.uk, May 2009
No I havent what would that tell? It would obviously give a lower gas rate as the burners come on and off every minute or so?

Jack, May 2009
have you gas rated it

b, May 2009
Like to think so!

Jack, May 2009
are you a gas engineer?

b, May 2009